GE imagination at work GE® Zoneline® - Efficient. Quiet. Reliable. Innovative.
Installation - Vertical Packaged Terminal Air Conditioners

Zoneline Vertical units give home-like appearance to hotels, motels, apartments, office buildings and more!

Power Connection Kits for 8500 Series

The ZVAC units have a universal heater assembly that is capable of producing electric resistance heat that can operate on a 15-amp, 20-amp, or 30-amp circuit. The amount of resistance heat is determined by the selection of the correct power connection kit. This is the same type of connection used by GE for years in the Premium and Deluxe series of the Zoneline units.

Units installed on 230 or 208-volt circuits may be line cord connected by plugging the line cord into a wall-mounted receptacle in the enclosure closet or directly connected. All ZVAC units come with a unit mounted junction box to contain the wiring connections if a direct connection installation is required. The same power connection kit is used for line cord connection or to make a direct connection. Instructions for making a direct connection on 230 or 208-volt circuits are included in the unit installation instructions.

Units installed on a 265-volt circuit must be direct connectedin accordance with National Electrical Code. All ZVAC units come with a unit mounted junction box to contain the wiring connections when direct connection installation is made.

RAK3152/3202/3302

RAK3152/3202/3302
230/208 volt cord connection kit

Related Links

230/208 Volt Line Cord Connected Units
Power Connection Kit RAK3152 RAK3202 RAK3302
Heater KW 2.55/2.09 3.45/2.82 5.00/4.09
Heater Amps 11.1/10.0 15.0/13.6 21.7/19.7
Minimum Circuit Amps 15 20 30
Recommended Protective Device 15 Amp Time Delay Fuse or Breaker 20 Amp Time Delay Fuse or Breaker 30 Amp Time Delay Fuse or Breaker
230/208 Volt Direct Connected Units
Power Connection Kit RAK4157 RAK4207 RAK4307
Heater KW 2.55/2.09 3.45/2.82 5.0/4.09
Heater Amps 11.0/10.0 15.0/13.6 21.7/19.7
Minimum Circuit Amps 15 20 30
Recommended Protective Device 15 Amp Time Delay Fuse or Breaker 20 Amp Time Delay Fuse or Breaker 30 Amp Time Delay Fuse or Breaker
265/277 Volt Direct Connected Units
Power Connection Kit RAK5157 RAK5207 RAK5307
Heater KW 2.55 3.452 5.0
Heater Amps 9.7 13.1 18.9
Minimum Circuit Amps 15 20 30
Recommended Protective Device 15 Amp Time Delay Fuse or Breaker 20 Amp Time Delay Fuse or Breaker 30 Amp Time Delay Fuse or Breaker

See the Architects & Engineers Design Data Manual for additional installation information.