Power Connection Kits for 7500 Series

The ZVAC units have a universal heater assembly that is capable of producing electric resistance heat that can operate on a 15 amp, 20 amp or 30-amp circuit. The amount of resistance heat is determined by the selection of the correct power connection kit.

Units installed on 230 or 208-volt circuits may be line cord connected by plugging the line cord into a wall-mounted receptacle in the closet or directly connected. ZVAC units come with a unit-mounted junction box to contain the wiring connections when direct connection installation is made. Connections must conform to local codes.

RAK3152/3202/3302

RAK3152/3202/3302
230/208 volt cord connection kit

Related Links

230/208 Volt Line Cord Connected Units
Power Connection Kit RAK3152 RAK3202 RAK3302
Heater KW 2.55/2.09 3.45/2.82 5.00/4.09
Watts 2,550/2,090 3,450/2,820 5,000/4,090
Heat Amps 11.1/10.0 15.0/13.6 21.7/19.7
Minimum Circuit 15 20 30
Recommended Protective Device 15 Amp Time Delay Fuse or Breaker 20 Amp Time Delay Fuse or Breaker 30 Amp Time Delay Fuse or Breaker
Plug Configuration 15 Amp Tandem 20 Amp Perpendicular 30 Amp Large Tandem
265 Volt Permanent Connected Units
Power Connection Kit RAK5157 RAK5207 RAK5307
Heater KW 2.55 3.45 5.0
Watts 2,550 3,450 5,000
Heat Amps 9.7 13.1 18.9
Minimum Circuit Amps 15 20 30
Recommended Protective Device 15 Amp Time Delay Fuse or Breaker 20 Amp Time Delay Fuse or Breaker 30 Amp Time Delay Fuse or Breaker
Plug Configuration 15 Amp Tandem 20 Amp Perpendicular 30 Amp Large Tandem

See the Architects & Engineers Design Data Manual for additional installation information.