Zoneline Vertical units give home-like appearance to hotels, motels, apartments, office buildings and more!
|
Power Connection Kits for 7500 Series
The ZVAC units have a universal heater assembly that is capable of producing electric resistance heat that can operate on a 15 amp, 20 amp or 30-amp circuit. The amount of resistance heat is determined by the selection of the correct power connection kit.
Units installed on 230 or 208-volt circuits may be line cord connected by plugging the line cord into a wall-mounted receptacle in the closet or directly connected. ZVAC units come with a unit-mounted junction box to contain the wiring connections when direct connection installation is made. Connections must conform to local codes.

RAK3152/3202/3302 230/208 volt cord connection kit
|
|
Related Links
|
| 230/208 Volt |
Line Cord Connected Units |
| Power Connection Kit |
RAK3152 |
RAK3202 |
RAK3302 |
| Heater KW |
2.55/2.09 |
3.45/2.82 |
5.00/4.09 |
| Watts |
2,550/2,090 |
3,450/2,820 |
5,000/4,090 |
| Heat Amps |
11.1/10.0 |
15.0/13.6 |
21.7/19.7 |
| Minimum Circuit |
15 |
20 |
30 |
| Recommended Protective Device |
15 Amp Time Delay Fuse or Breaker |
20 Amp Time Delay Fuse or Breaker |
30 Amp Time Delay Fuse or Breaker |
| Plug Configuration |
15 Amp Tandem |
20 Amp Perpendicular |
30 Amp Large Tandem |
| 265 Volt |
Permanent Connected Units |
| Power Connection Kit |
RAK5157 |
RAK5207 |
RAK5307 |
| Heater KW |
2.55 |
3.45 |
5.0 |
| Watts |
2,550 |
3,450 |
5,000 |
| Heat Amps |
9.7 |
13.1 |
18.9 |
| Minimum Circuit Amps |
15 |
20 |
30 |
| Recommended Protective Device |
15 Amp Time Delay Fuse or Breaker |
20 Amp Time Delay Fuse or Breaker |
30 Amp Time Delay Fuse or Breaker |
| Plug Configuration |
15 Amp Tandem |
20 Amp Perpendicular |
30 Amp Large Tandem |
See the Architects & Engineers Design Data Manual for additional installation information.
|